Temperature Sensors
Application:
Temperature sensor type CZT-1 is intended to supervise the temperature of devices components, as well as non-aggresive liquids: water, oils, oil-water emulsions etc.
The sensor cannot be used to control the temperature of aggresive media.
Performance:
Temperature sensor is equipped with bimetallic bistable thermostat. Under the influence of temperature, opens or shorts the sensor contacts, as a result closes or cuts the control loop of a device, where the sensor was adopted. Thereby the automatic stop of a device is possible, in case the permissible temperature exceeds its limits.
Technical data:
Max voltage | 50 V |
Max current Ii | 6 A |
Internal capacity Ci | negligible |
Internal inductance Li | negligible |
Temperature of opening/closing the contact | 30-150 °C (Table 1 and 2) |
Type of contact | NC or NO |
Wire lenght | up to 20 m |
Fitting thread |
metric M8x1 ÷ M27x2 inch G¼’’÷ G1 ½’’ |
Max working pressure | 30 bar |
Ambient temperature | -20°C ÷ +40°C |
Air humidity | up to 95% at temp. 40°C |
Altitude relative to sea level | -2000 ÷ 1000 m |
Table 1: Temperatures of opening and closing the contacts of sensor, contact NC
Temperature of opening the contact (°C | Temperature of closing the contact (°C) |
---|---|
30 ± 3 | 15 ± 4 |
40 ± 3 | 25 ± 6 |
50 ± 3 | 35 ± 6 |
60 ± 3 | 45 ± 6 |
70 ± 3 | 55 ± 6 |
80 ± 3 | 65 ± 6 |
90 ± 3 | 75 ± 6 |
100 ± 4 | 80 ± 7 |
110 ± 4 | 90 ± 7 |
120 ± 4 | 98 ± 6 |
130 ± 4 | 110 ± 8 |
140 ± 4 | 115 ± 8 |
150 ± 4 | 120 ± 8 |
Table 2: Temperatures of opening and closing the contacts of sensor, contact NO
Temperature of closing the contact (°C) | Temperature of opening the contact (°C |
---|---|
35 ± 3 | 50 ± 6 |
45 ± 3 | 60 ± 6 |
65 ± 3 | 80 ± 6 |
75 ± 3 | 90 ± 6 |
80 ± 4 | 100 ± 7 |
100 ± 4 | 120 ± 7 |
115 ± 4 | 140 ± 8 |
Hydro Elektra is able to provide not only the sensors with threshold temperature and/or the liquid level measurement but also with continuously reading parameters using a current or voltage interface.